Bus Cable Profibus Devicenet Profinet Industrial Cables
Electrical data
Characteristic impedance: | 100 Ohm ± 20 % | 100 Ohm ± 20 % |
Conductor resistance, max.: | 22 Ohm/km | 22 Ohm/km |
Insulation resistance, min.: | 1 GOhm x km | 1 GOhm x km |
Loop resistance: | 44 Ohm/km max. | 44 Ohm/km max. |
Mutual capacitance: | 60 nF/km nom. | 60 nF/km nom. |
Nominal voltage: | 300 V | 300 V |
Test voltage: | 2,5 kV | 2,5 kV |
Attenuation: | 39 kHz ≤ 3,0dB/km | 39 kHz ≤ 3,0 dB/km |
Application
Used for normal requirements in the process automation field (chemical industry). The colour blue identifies it as suitable for use in potentially explosive areas (and ATEX/ Class II, EX-i/ EN 60079-14). For other applications, the colour black is usually selected.
Specification
Inner conductor diameter: Core insulation:
Core colours: Stranding element: Separator: Shielding 1:
Total shielding:
Outer sheath material: Cable external diameter: Outer sheath colour:
Electrical data
Hazardous areas 1x2x1.0/2.55 mm
Copper, bare (AWG 18/1) PE
Rd, gn
2 cores + 2 fillers stranded together Polyester foil over stranded bundle Al-Foil
Cu braid, tinned PVC
App. 7,6 mm ± 0,2 mm Blue similar to RAL 5015




Hot Tags: bus cable profibus devicenet profinet industrial cables, China, manufacturers, suppliers, factory, wholesale, custom, Vietnam